Automatic water level controller | stainless steel probe | sensor probe | DF96 level switch

Automatic water level controller | stainless steel probe | sensor probe | DF96 level switch
 

Product description:

Product parameters:

  • Brand: MYCN
  • Model: Probe
  • NO
  • DF-96D + probe DF-96B + probe DF-96C + probe the DF-96D + probe the DF-96D + probe the DF-96D + probe the DF-96D +
  • Decoration and construction content: hydropower projects



Note: This baby weight with packaging weight 0.06KG or so, the weight is for reference only


DF96 series of water level controller sensor probe, and our sales of DF96 series supporting the use of water level controller, standard wiring length of 2 meters.

(A) single-control upper pool wick installation instructions Installation diagram shown in Figure 1:

A (warp) - for the upper pool (water tower) limit level control point, the water level up to point A water level, water and probe contact, the water controller automatically shut down;

B (blue line) - for the upper pool (water tower) lower level control point, the water level dropped to B below the water level, the water and the probe out of contact, the water level controller automatically open pump,

C (black line) - for the pool (water tower) ground wire, placed in the lowest point of the pool contact with the bottom of the pool;

D (green line), and E (yellow line).

(B) single control of the pool (ie drainage basin) Probe Installation Installation diagram shown in Figure 2:

E-level control point for the upper pool, the water up to the water level E point, the water contact with the probe, the water level controller automatically open the pump, the pool drainage; if not drainage, the E point is not connected;

D-level control point for the lower pool, the water level dropped to D level, the water and the control head disengagement, the water level controller automatically shut down the pump, the pool stop the drainage;

C - for the pool ground wire, put the lowest point of the pool of water contact with the bottom;

A, B points are not connected.

(C) water protection probe installation instructions Installation diagram shown in Figure 3:

C, D point for the pool water level lower limit control point, the water level down to the lower water level, C, D probe out of contact with the water, the water level controller relay action, cut off the output, the pump stops working;

E point and C point shorted;

A, B points are not connected.

(D) joint control of the upper and lower pool probe installation diagram shown in Figure 3:

A-level for the upper pool (water tower) level control point, the water level up to point A water level, the water contact with the control head, the water controller automatically shut down the pump;

B- for the upper pool (water tower) the lower limit of liquid control point, the water level dropped to B below the water level, the water and the probe out of contact with the water level control automatically open pump, the pool filled with water;

C- for the upper and lower pool (water tower) public online, on the bottom of the pool and the bottom of the pool contact;

D-level control point for the lower pool, the water level dropped to the D-point water, water and the probe out of contact, the water level controller automatically shut down the pump, the pool stop the drainage;

E-level limit for the lower pool control point, the water level rose to the E point of water, water and probe contact, the water level controller automatically open the pump, the first row of the pool, if not drainage, the E point is not connected.

The installation uses additional instructions

1, in order to ensure that the liquid level controller to work properly, please re-check the input and output wiring, the probe cable is reliable contact can be moved up and down the probe to contact, from the water, simulate the water controller is Installation is correct and can work as you need.

2, It is recommended to fix the probe to the inner wall of the pool so as to avoid the misalignment of the water level controller due to the offset of the probe position. (If the wall of the water tank is metal, it should not be connected to the inner wall except for the C point ground wire to avoid short circuit, Controller does not work properly).

3, according to the wiring method is connected, check the product on the right side of the 'manual / automatic' switch (DF-96D no), whether the user can manually open and close the pump, adjust it back to ' Position, water level controller into working condition.

4, the temporary need to open and close the pump, please use the left side of the water level controller 'manual / automatic' switch control (DF-96D) without manual switch.

5, in order to avoid malfunction, do not install the product in the wet, corrosion and high metal content of the gas environment.

6, we recommend supporting the use of the company's water level control dedicated probe.

Troubleshooting

1, connected to the power does not work:

A. Check if the red power indicator light is on, if not, check whether the input and output terminals have been in good contact;

B. Check the 'Manual / Auto' switch on the left side of the product, adjust it back to the 'Auto' position on the 'Off' position, and the water level controller will enter the working state.

2, the water level line exceeds or below the probe control point, the pump does not automatically shut down or open, please press the 'automatic / manual' switch manually control the water pump and check:

A. Whether the probe is deviated from the original position, the position is too high (too low), resulting in the water level can not contact (off);

B. Whether the connection of the upper and lower water line and the ground probe is dislocated with other lines, whether there is a wrong connection or short circuit;

C. Whether the probe corrosion and shedding phenomenon, the probe line and the product, the probe line and the connection between the probe is in good contact;

D.C point ground wire has been placed in the lowest position of the pool.