Wenhui battery 12V100AH ​​| lead acid maintenance-free battery UPS power supply / EPS / DC screen / toy-specific

Wenhui battery 12V100AH ​​| lead acid maintenance-free battery UPS power supply / EPS / DC screen / toy-specific
 

Product description:

Product parameters:

  • Condition: New
  • Brand: Wenhui
  • Model: 12V100AH


Battery installation and maintenance

First, the battery installation

1. The actual capacity of the same battery or battery can only be used in tandem.

2. The actual voltage of the same battery or battery can be used in parallel.

3. Battery connection should be strong, to prevent the use of the process of spark.

4. Do not reverse or short circuit.

5. Install the battery using insulated tools, wear insulated gloves.

Second, the use of the battery charge

1, floating charge: constant current limiting charge mode, the charging voltage 13.60 ~ 13.80V (25 ℃), the maximum charge current shall not exceed 0.25 times the nominal capacity.When the temperature is not 25 ℃, the temperature and voltage Compensation, the coefficient of -24mv / ℃.

2, recycling: the use of constant voltage limiting charge, That is, the charging voltage 14.60 ~ 14.80V (25 ℃), the maximum charge current of not more than 0.25 times the nominal capacity.When the temperature is not 25 ℃, should be temperature and voltage compensation, coefficient -24mv /

3, the battery is charged factory, can be used directly, without the use of pre-charge. Long time to put the battery, every 2 to 3 months is best to make a supplementary charge, charging can be used (1).

Third, the daily maintenance of the battery

1, every 2 to 3 months to conduct a maintenance of the battery charge and discharge, that is, the battery in the device for an effective charge and discharge to activate the battery within the active substance. Battery discharge to the device after the alarm into the charge, the charge voltage14.60~14.80V(25℃), When the temperature is not 25 ℃, should be temperature and voltage compensation, the coefficient of -24mv / ℃.

2, once a year to check a solid part of the battery connection, if loosening, timely fastening.

3, quarterly with a soft dry fabric wipe the surface of the battery.

Fourth, the matters needing attention

1, can not mix old and new batteries.

2, the battery can not be sealed in the battery charge and discharge use.

3, the battery should be evenly when handling, to avoid damage to the battery shell or short column.

4, the battery should be stored in a dry, ventilated place, avoid direct sunlight, away from heat.

Wenhui brand maintenance-free lead-acid battery UPS power by "GB / T valve sealed lead-acid battery standard" design and manufacture of products without the need to add water before use, the user can simply use the correct installation. Batteries with acid-free leakage, Resistance, vibration resistance, anti-over-discharge recovery ability, self-discharge, long life and so on.

Baby Features:
No need to add water, no need to add electrolyte, maintenance-free; easy connection, no specific direction to use; within the yin small, high output power; low impedance design, low self-discharge low self-discharge, no leakage, no acid pollution; , Capacity retention and storage time at 20 ℃ for 12 months or more; CCDS charge and discharge detection system to ensure product consistency; high-strength engineering plastics as raw materials and high-density ultra-fine glass fiber separator to ensure that the battery-class quality ; To adapt to a variety of temperature conditions (-15 ℃ -45 ℃); no free electrolyte, explosion-proof, self-discharge small.

Performance and Benefits:
★ high security and reliability
The use of fully automatic safety valve (VRLA), can prevent the gas is sucked into the battery to affect its performance, but also to prevent the gas generated by charging and other internal pressure caused by abnormal damage to the battery.Full sealed battery in the normal float will not have Electrolyte and acid mist discharged at the same time, the use of independent patented technology battery tray and supporting the use of batteries to ensure more safe use of battery.

★ long service life
In the environment of 20 ℃, FM series of small sealed battery float life of up to 3 to 5 years, FM fixed sealed battery float life of up to 8 to 10 years, FML series battery float life of up to 10 years, FMH series battery Floating life of up to 10 years, GFM series of floating-cell life of up to 15 years.

★ self-discharge rate is low
The use of special lead-calcium multi-alloy, the separator, the electrolyte and the production process of strict control of impurities in the 20 ℃ environment, KSTAR storage battery in 6 months without additional power to normal use.

★ conductive ability
Copper-plated terminal and specially designed to ensure excellent electrical performance.

★ ability to adapt to the environment
Can be used in the ambient temperature of -20 ℃ ~ + 50 ℃, suitable for desert, highland climate, can be used for special power supply.

★ strong direction
Special diaphragm (AGM) to firmly adsorb the electrolyte so that it does not flow. Battery, whether standing or lying will not leak to ensure the normal use.

★ green pollution-free
Mute, and no pollutants discharged. Battery room without acid-proof anti-corrosion measures, with electronic equipment and other equipment with a room.

model Voltage capacity Reference weight Dimensions
(V) (Ah) (Kg) L * W * H (mm)
6-GFM-7 12 7 2.0 115*65*94
6-GFM-17 12 17 4.5 180*77*167
6-GFM-24 12 24 7 165*125*175
6-GFM-38 12 38 10 197*165*175
6-GFM-65 12 65 16 350*166*175
6-GFM-100 12 100 23

407*173*210