0.6\1kV Cold Shrink Termination and Straight Through Joint

0.6\1kV Cold Shrink Termination and Straight Through Joint
 

Product description:

0.6/1kV Cold Shrink Termination and Straight Through Joint

Performance Standard: IEC60502.4; GB12706.4

Characteristics:

1. Cold shrink, which is also called Pre-expanded, is based on the characteristic of rubber that holds flexible memory. Furthermore, the flexible rubber is pre-expanded by mechanical ways during one flexible range and then inserted the plastic tubing to be fixed, While installation, Pull off the plastic tubing, the flexible rubber will shrink automatically and be wrapped onto the cable.

2. It's easy to operate while installation and meanwhile no other professional tools needed.

3. It's safe because of no fire.

4. It can make radical pressure onto the cable for long time and furthermore keep synchronous breath with cable. It has nicer performance of water-proof and sealling so that the accessory can function safely in a long time.
Order Reference


TYPE/ ORDER NUMBER

NAME

CABLE RANGE

1kV TLY 1 *25-50

TERMINATION FOR 1kV

1 CORES CABLE

25-50

1kV TLY 1 *70-120

70-120

1kV TLY 1 *150-240

150-240

1kV TLY 1 *300-400

300-400

1kV TLY 4 *25-50

TERMINATION FOR 1kV

4 CORES CABLE

25-50

1kV TLY 4 *70-120

70-120

1kV TLY 4 *150-240

150-240

1kV TLY4 *300-400

300-400

1kV TLY 5 *25-50

TERMINATION FOR 1kV

5CORES CABLE

25-50

1kV TLY 5 *70-120

70-120

1kV TLY 5 *150-240

150-240

1kV TLY 5 *300-400

300-400

1kV JLY 1 *25-50

STRAIGHT THROUGH JOINT
FOR 1kV 1 CORES CABLE

25-50

1kV JLY 1*70-120

70-120

1kV JLY 1*150-240

150-240

1kV JLY1 *300-400

300-400

1kV JLY 4*25-50

STRAIGHT THROUGH JOINT
FOR 1kV 4 CORES CABLE (3+1)

25-50

1kV JLY 4 *70-120

70-120

1kV JLY4 *150-240

150-240

1kV JLY 4 *300-400

300-400

1kV JLY 5 *25-50

STRAIGHT THROUGH JOINT
FOR 1kV 5 CORES CABLE

25-50

1kV JLY 5 *70-120

70-120

1kV JLY 5 *150-240

150-240

1kV JLY 5 *300-400

300-400


Technical index


Item

Test Item

Standard require

Test result

Note


1kV in/ outdoor terminations and joints

1min Power frequency test

4kV 1min no flash over, no strick

4kV. 1min combination sample no flash, no strick no flash over

Pass

Cyclic load test

5h heating, conductiontemperature 95℃, 3h colling

Subjected to 3 time Cyclic load test

Remarked by the

next test

4h Power frequency test

2.4KV 4h no flash over, no strick

2.4kV 4h Combination sample no strick, no flash over

Pass