Four limit alarm -KH102D

Four limit alarm -KH102D
 

Product description:

Four limit alarm -KH102D


Four limit alarm -KH102D

product manual:
Four limit alarm -KH102D


On the basis of KH102 function adds dual communication functions (both computer communications, but communications and infrared scanning gun), with manual and automatic trigger input display the scanned product is qualified. (For details, refer KH102 Operating Instructions) applies temperature, pressure, liquid level, gravity, instantaneous flow of accurate measurement of physical quantities and alarm. with a variety of auxiliary functions communication, transmission, feed, etc. universal input adapter multiple transmission signal output using the most advanced modular structural, functional and flexible preparation, alarm resistance state can be arbitrarily set upper and lower limits, upper limit and lower limit. Using the most common MODBUS communication protocol, the maximum baud rate of 19200
First, the main technical indicators
• Accuracy: ± (0.2% FS + 1) word
• Sampling period: ≤0.5 seconds
• Power supply voltage: 85-240VAC
• thermocouple cold junction compensation: internal or external compensation components CU50 compensation
• Power consumption: (5W
• Burnout or Overrange: Display OPEN
• using SMD (SMT) technology, design more compact, lightweight
• Input Specifications:
Thermocouple: K, S, E, J, T, B, N
Thermal resistance: PT100, CU50, CU100
Linear voltage: 0-5V, 1-5V
Linear current: 0-10mA, 4-20mA
Extended Specifications: while retaining the above inputs.
Customer specified an additional input specifications
• Output Module Specifications:
R1A: relay output (0.8A normally open)
R1B: Relay output (0.8A normally closed)
R1C: relay output (0.8A normally open + normally closed)
R2A: relay output (3A normally open)
R2B: relay output (3A normally closed)
R2C: relay output (3A normally open + normally closed)
W1: SCR non-contact output (100-240VAC / 0.2A)
G: solid state relay driving voltage (DC12V / 50mA output)
K1: Single SCR zero trigger
K2: Dual SCR zero trigger
I1: optically isolated current transmission output
S1: optically isolated RS485 communication port
S2: optically isolated RS232 communication port
U1 / U2 / U3: Isolated 5V / 12V / 24VDC feed