AND48 series of communications power inverter

AND48 series of communications power inverter
 

Product description:

Input voltage: 1 (V) Waveform distortion: 1 (%) Frequency regulation of: 1 (%)
Output voltage: 1 (V) Load regulation: 1 (%) Circuit mode: SPWM switching
Load Type: Mixed loads Custom processing: Efficiency: 1 (%)
Applications: IT industry Type: Regulator power inverter Model: AND48
Output frequency: 1 (Hz) Brand: ACS Product Certification: ROHS
Control mode: Pulse width modulation type Input Frequency: 1 (Hz)

AND48 series of communications power inverter

(Introduction)

西安杰瑞达 Instrument Co., Ltd. is a manufacturer with international authority recognized ISO9001 international quality standard management system. Specialized in producing power equipment. Inverter device is a DC electrical energy into uninterrupted, clean AC power The conversion means to provide computers and other electrical equipment can be used continuous AC power, preparedness and unstable mains power. can also prevent distortion of public communication of all kinds, such as the supply voltage drops, surge, spikes and Radio frequency interference.

(Features)

• Fully isolated inverter technology, no noise pure sinusoidal AC output voltage;

• The inverter unit with microprocessor control; SPWM sinusoidal pulse width modulation technique; waveform pure;

• unique dynamic current loop control technology to ensure reliable operation of the inverter;

• overload capacity, can withstand computer load power surge;

• High-power static bypass switch; by the bypass when the overload; switching time is short;

• With input over; undervoltage; output over; undervoltage; over-temperature; short circuit protection;

• The inverter front panel LED display, status at a glance;

• Multiple lightning protection scheme option;

(working principle)

Communication dedicated inverter system working block diagram: As shown in Figure 1

Figure 1 Communication dedicated inverter system architecture block diagram

A. inverter system operates in various parts of the bypass state circuit works: After entering through mains EMI filter to filter out noise interference sent mains end, after sending the static switch via the output EMI filter to remove After the interference to the user load terminals, providing power for the user load. machine output at this time is just after filtering without voltage, frequency stabilization process in the ordinary mains.

Figure 2 inverter system working methods of operation of the various parts of the circuit to bypass state

B. inverter system operates in various parts of the circuit works when the DC power supply normal state, when the utility power fails, the DC voltage is supplied to the inverter input side, in the main control circuit driving the inverter DC power into voltage, frequency stability, without interference pure sine wave output to the static switch, the static switch of this high-quality power to the output after EMI filters, EMI filters out interference after the load to the end user, to provide users with high-quality power supply.

Figure 3 inverter system working methods of operation of the various parts of the circuit to the battery when the normal power supply status

(Main Specifications)

Model (AND48-)

1005

1010

1020

1030

1050

1080

1100

Rated Capacity

500VA

1KVA

2KVA

3KVA

5KVA

8KVA

10KVA

Operation mode

Pure Inverter

DC input

Rated voltage (V)

48VDC

Voltage range (V)

40 ~ 55 VDC

Current (A)

10.4

20.8

41.6

62.5

104.2

166.7

208.3

AC bypass input

Input voltage range (VAC)

220±15%

Enter the maximum current (A)

2.3

4.5

9

13.6

23

36

45

Switching time (mS)

4ms

AC output

Rated power (KW)

0.4

0.8

1.6

2.4

4

6.4

8

Rated Current (A)

2.3

4.5

9

13.6

23

36

45

Power factor (PF)

0.8

Output voltage accuracy

AC220 V ± 1%

Waveform

Sine wave

Output frequency accuracy (Hz)

50HZ ± 0.1%

Waveform distortion (THD)

≤3%

Changes in an instant

± 5% (0 ~ 100% load)

Crest factor (CF)

3: 1

Inverter efficiency (%)

90 (80% resistive load)

92 (80% resistive load)

Insurance

Protect

Output overload protection

150%, maintained 30S

Output short circuit protection

Shutdown protection, artificial restoration

DC low voltage protection

Inverter shutdown, automatic recovery

Over-temperature protection system

85 ℃ shutdown protection, 75 ℃ automatically restored

Enter the reverse protection

no work

working environment

Noise (1 meter)

≤40db

Dielectric strength

Input to output 3000VAC, 1 分钟

Working temperature

-10~45℃

Relative humidity

20% to 90% non-condensing

Altitude (m)

≤1000

cooling method