XSC5 Series PID regulator

XSC5 Series PID regulator
 

Product description:

Explanation
① basic error is better than ± 0.2% F · S, 16 bit A / D converter, measurement and control cycle 0.2 seconds, self-tuning
② anti-jamming design, inhibit the rapid burst interference relays, contactors, etc. produced by the scene and other electromagnetic interference, immunity to level III
③ Input signal: thermal resistance, thermocouple, DC current, DC voltage, remote pressure gauge, etc.
④ Dimensions: 160 * 80 (horizontal / vertical), 96 * 9696 * 48 (horizontal / vertical), 72 * 7248 * 48
⑤ Instrument Power: 220V AC (9 ~ 30) V DC.
⑥ hand / auto switch
basic configuration
Dual display and control output
extensions
① alarm output: 160 * 8096 * 9696 * 48 in three sizes can add up to 3:00; 72 * 7248 * 48 may add 1 point
② transmission output
③ external power supply (24V or 12V)
④ Communication Interface: RS 232 or RS 485

Selection Tables

content
Code Description
XSC5 /
PID smart regulation, dual display, control output
shape
size
A―
160 (W) * 80 (H) * 125 (L) or 80 (W) * 160 (H) * 125 (L)
B―
96 (W) * 96 (H) * 112 (L)
C―
96 (W) * 48 (H) * 112 (L) or 48 (W) * 96 (H) * 112 (L)
D-
72 (W) * 72 (H) * 112 (L) (limit XSC5)
E―
48 (W) * 48 (H) * 112 (L) (limit XSC5)
Panel form
H
Horizontal
S
Vertical
F
Square
Input signal
(When the input signal ordering others)
E
Thermocouple K, S, R, B, N, E, J, T or radiation temperature meter
R
RTD Pt100, Cu100, Cu50, BA1, BA2, G53 or resistance
I
DC current (4 ~ 20) mA. (0 ~ 10) mA or (0 ~ 20) mA
V
DC voltage (0 ~ 5) V, (1 ~ 5) V
M
DC mV (ordering range)
W
Potentiometer 500Ω ~ 5000Ω
L
Remote pressure gauge
Number of alarm points
T•
T0: No alarm T1 ~ T3: 1 ~ 3-point alarm
Control Output
C0
No output
C1
Current output (4 ~ 20) mA. (0 ~ 10) mA or (0 ~ 20) mA
C2
Voltage output (0 ~ 5) V, (1 ~ 5) V
C3
Voltage output (0 ~ 10) V
C4
Solid state relay drive output voltage
C5
SCR non-contact normally open output
C6
SCR zero trigger output
C7
Relay contact switch output
Transmission output
(Independent power supply, full isolation. 10 D / A, the error is less than ± 0.5%, or 12 D / A, the error is less than ± 0.2%)
A0
No output
A1
Current output (4 ~ 20) mA. (0 ~ 10) mA or (0 ~ 20) mA
A2
Voltage output (0 ~ 5) V, (1 ~ 5) V
A3
Voltage output (0 ~ 10) V
A4
Other output
External power supply
B0
No external power supply
B1
External supply 24V DC
B2
External supply 12V DC
B3
Outside for precision voltage source
B4
Outside for precision current source
B5
other
Communication Interface
(Independent power supply, full isolation, 2400 ~ 19.2K instrument addresses 0 to 99, the response delay is less than 500μs)
S0
No communication interface
S1
RS-232 Interface
S2
RS-485 Interface
Instrument Power
V0
220V AC
V1
24V DC
V2
12V DC
V3
other

Instructions free of charge Phone: 400-676-6002