XSM Series speed, line speed, frequency measurement and control instrument

XSM Series speed, line speed, frequency measurement and control instrument
 

Product description:

Explanation:
① connected with various types of proximity switches, encoders, or various types of pulse measurement speed, frequency, line speed, measurement frequency range 0.1Hz ~ 25kHz, the basic error of ± 0.02%, 5-digit LED display
② Dimensions: 160 * 80 (horizontal), 96 * 48 (horizontal), 96 * 96
③ instrument power 220V AC. (9 ~ 30) V DC
basic configuration:
Single display, external power supply for sensors (≥50mA)
extensions:
① alarm output: 160 * 80 specifications up to 4:00, 96 * 48 up to 2:00
② transmission output
③ Communication Interface: RS 232 or RS 485

Selection Tables

,
content
Code Description
XSM /
Single display, external power supply for sensors (≥ 50mA)
shape
size
A
160 (W) *80 (H) *125 (L)
B
96 (W) *96 (H) *112 (L)
C
96 (W) *48 (H) *112 (L)
Panel form
H
Horizontal
F
Square
display method
(LED Colors by order request)
1
Measured value (green)
2
Measured value (green) + Set value (red) (limited A Type instrument)
3
Measured value (green) + Measurement light beam (green) (limited A Type instrument)
Input signal
G
Standard applicable to NPN, PNP Type voltage pulses. (4~20) mA 2 Restrictions pulses. TTL Pulse, etc.
M
mV Type, suitable to the magnetic-electric proximity switches
Number of alarm points
T•
T0: No alarm T1 ~ T8: 1~8 Point alarm
Transmission output
( Independent power supply, full isolation.10 Location D / A. Error is less than ±0.5% ,or 12 Location D / A. Error is less than ±0.2%)
A0
No output
A1
Current output (4~20) mA ,(0~10) mA or (0~20) mA
A2
Voltage output (0~5) V,(1~5) V
A3
Voltage output (0~10) V
A4
Other output
External power supply
B0
No external power supply
B1
External supply 24V DC Error is less than ±5%, 50mA
B2
External supply 12V DC Error is less than ±5%, 50mA
B3
other
Communication Interface
(Independent power supply, full isolation.2400~19.2K Instrument address 0~99 , The response delay is less than500μs,)
S0
No communication interface
S1
RS-232 interface
S2
RS-485 interface
S3
RS-422 interface
S4
BCD Code Interface (limited A,B Type instrument) Note2
Instrument Power
V0
220V AC
V1
24V DC
V2
12V DC
V3
other
Print function (limit A,B Type instrument)
P
P It indicates that the print interface can be omitted without
Prescale unit
F*
F * represents the prescale unit, can be omitted without.
Non-standard features
N
N It represents a non-standard function